DC watts to amps
I (A) = P (W) ÷ V (V)Batteries, solar panels, RVs, boats and car electronics run on DC. A 300 W fridge on a 12 V battery draws 300 ÷ 12 = 25 A.
Free electrical calculator for DC, 1-phase and 3-phase
This watts to amps calculator converts power to current, or amps back to watts, for DC, single-phase and three-phase circuits. Add the power factor or motor horsepower and instantly see the right breaker size, how loaded your circuit is and the full working.
Follows the voltage, circuit type and power factor you set above.
| Power | Current | Breaker (125%) |
|---|---|---|
| 100 W | 0.833 A | 15 A |
| 200 W | 1.67 A | 15 A |
| 300 W | 2.5 A | 15 A |
| 500 W | 4.17 A | 15 A |
| 750 W | 6.25 A | 15 A |
| 1,000 W | 8.33 A | 15 A |
| 1,200 W | 10 A | 15 A |
| 1,500 W | 12.5 A | 20 A |
| 1,800 W | 15 A | 20 A |
| 2,000 W | 16.67 A | 25 A |
| 2,500 W | 20.83 A | 30 A |
| 3,000 W | 25 A | 35 A |
| 4,000 W | 33.33 A | 45 A |
| 5,000 W | 41.67 A | 60 A |
| 7,500 W | 62.5 A | 80 A |
| 10 kW | 83.33 A | 110 A |
Formulas
Current depends on three things: the power of the load, the supply voltage and, for AC, the power factor. Pick the formula that matches your circuit. Every example below can be checked with the calculator above.
I (A) = P (W) ÷ V (V)Batteries, solar panels, RVs, boats and car electronics run on DC. A 300 W fridge on a 12 V battery draws 300 ÷ 12 = 25 A.
I = P ÷ (V × PF)Home outlets are single-phase: 120 V in North America and 230 V in most other countries. A 1,500 W load at 230 V with a power factor of 0.95 draws 1,500 ÷ (230 × 0.95) = 6.86 A.
I = P ÷ (√3 × V(LL) × PF)Use this with the voltage between two phases, such as 208 V, 400 V or 480 V. A 10 kW motor load at 400 V and PF 0.85 draws 10,000 ÷ (1.732 × 400 × 0.85) = 16.98 A per line.
I = P ÷ (3 × V(LN) × PF)Use this with the phase to neutral voltage, such as 230 V or 277 V. The same 10 kW load at 230 V and PF 0.85 draws 10,000 ÷ (3 × 230 × 0.85) = 17.05 A per line.
Need amps to watts instead? Rearrange the same formulas: P = V × I for DC, P = V × I × PF for single-phase and P = √3 × V × I × PF for three-phase. For example, a 20 A circuit at 240 V carries up to 4,800 W. For resistance and voltage problems, try the Ohm’s law calculator.
Reference
Amps for common wattages at the most used voltages, assuming a resistive load (power factor 1). For motors, compressors and other inductive loads, divide each value by the power factor, or set it in the calculator for an exact answer.
| Watts | 12 V DC | 24 V DC | 120 V | 230 V | 240 V | 400 V 3-phase | 480 V 3-phase |
|---|---|---|---|---|---|---|---|
| 100 W | 8.33 A | 4.17 A | 0.83 A | 0.43 A | 0.42 A | 0.14 A | 0.12 A |
| 200 W | 16.67 A | 8.33 A | 1.67 A | 0.87 A | 0.83 A | 0.29 A | 0.24 A |
| 300 W | 25.00 A | 12.50 A | 2.50 A | 1.30 A | 1.25 A | 0.43 A | 0.36 A |
| 500 W | 41.67 A | 20.83 A | 4.17 A | 2.17 A | 2.08 A | 0.72 A | 0.60 A |
| 750 W | 62.50 A | 31.25 A | 6.25 A | 3.26 A | 3.13 A | 1.08 A | 0.90 A |
| 1,000 W | 83.33 A | 41.67 A | 8.33 A | 4.35 A | 4.17 A | 1.44 A | 1.20 A |
| 1,200 W | 100.0 A | 50.00 A | 10.00 A | 5.22 A | 5.00 A | 1.73 A | 1.44 A |
| 1,500 W | 125.0 A | 62.50 A | 12.50 A | 6.52 A | 6.25 A | 2.17 A | 1.80 A |
| 1,800 W | 150.0 A | 75.00 A | 15.00 A | 7.83 A | 7.50 A | 2.60 A | 2.17 A |
| 2,000 W | 166.7 A | 83.33 A | 16.67 A | 8.70 A | 8.33 A | 2.89 A | 2.41 A |
| 2,500 W | 208.3 A | 104.2 A | 20.83 A | 10.87 A | 10.42 A | 3.61 A | 3.01 A |
| 3,000 W | 250.0 A | 125.0 A | 25.00 A | 13.04 A | 12.50 A | 4.33 A | 3.61 A |
| 3,500 W | 291.7 A | 145.8 A | 29.17 A | 15.22 A | 14.58 A | 5.05 A | 4.21 A |
| 4,000 W | 333.3 A | 166.7 A | 33.33 A | 17.39 A | 16.67 A | 5.77 A | 4.81 A |
| 5,000 W | 416.7 A | 208.3 A | 41.67 A | 21.74 A | 20.83 A | 7.22 A | 6.01 A |
| 6,000 W | 500.0 A | 250.0 A | 50.00 A | 26.09 A | 25.00 A | 8.66 A | 7.22 A |
| 7,500 W | 625.0 A | 312.5 A | 62.50 A | 32.61 A | 31.25 A | 10.83 A | 9.02 A |
| 10,000 W | 833.3 A | 416.7 A | 83.33 A | 43.48 A | 41.67 A | 14.43 A | 12.03 A |
Appliances
Typical running wattage and current for everyday appliances. Your device label gives the exact rating, and motors or compressors can briefly draw 3 to 7 times more current at start-up. To see what these loads cost to run, use the electricity cost calculator.
| Appliance | Typical watts | Amps at 120 V | Amps at 230 V | Amps at 240 V |
|---|---|---|---|---|
| LED bulb | 10 W | 0.08 A | 0.04 A | 0.04 A |
| Laptop charger | 65 W | 0.54 A | 0.28 A | 0.27 A |
| Ceiling fan | 75 W | 0.63 A | 0.33 A | 0.31 A |
| 55-inch LED TV | 100 W | 0.83 A | 0.43 A | 0.42 A |
| Refrigerator (running) | 150 W | 1.25 A | 0.65 A | 0.63 A |
| Desktop PC | 300 W | 2.50 A | 1.30 A | 1.25 A |
| Washing machine | 500 W | 4.17 A | 2.17 A | 2.08 A |
| Microwave oven | 1,000 W | 8.33 A | 4.35 A | 4.17 A |
| Toaster | 1,200 W | 10.00 A | 5.22 A | 5.00 A |
| Space heater | 1,500 W | 12.50 A | 6.52 A | 6.25 A |
| Air conditioner (1.5 ton) | 1,700 W | 14.17 A | 7.39 A | 7.08 A |
| Hair dryer | 1,800 W | 15.00 A | 7.83 A | 7.50 A |
| Electric kettle | 2,000 W | 16.67 A | 8.70 A | 8.33 A |
| Water heater (tank) | 4,500 W | 37.50 A | 19.57 A | 18.75 A |
| Clothes dryer | 5,000 W | 41.67 A | 21.74 A | 20.83 A |
| Level 2 EV charger | 7,200 W | 60.00 A | 31.30 A | 30.00 A |
Why ours
Most converters stop at one formula and one direction. This one covers the questions you actually have when planning a circuit.
Switch between watts to amps and amps to watts without opening another page. Enter power in W, kW or HP and current in A or mA.
DC, AC single-phase and AC three-phase, with a clear choice between line to line and line to neutral voltage so the √3 factor is never misapplied.
Use the slider or presets for resistive, LED and motor loads. You also get apparent power in kVA and reactive power in kVAR.
See the next standard NEC or IEC breaker at 125% of the load, then check what share of a 15 A, 16 A or larger circuit you are using.
Each result lists the formula with your numbers plugged in, so you can verify it, learn from it or paste it into a report.
Runs entirely in your browser with no sign-up and no tracking of your inputs. Copy the answer or share a link that reopens the same calculation.
Guide
Getting an answer takes a few seconds. Results update as you type, so you can try different voltages or loads instantly.
Select Watts → Amps to find current, or Amps → Watts to find power.
Pick DC for batteries and solar, AC 1-phase for home outlets, or AC 3-phase for commercial and industrial supplies.
Type the wattage or tap an appliance, then choose a voltage chip. For motors, switch the unit to HP and add the efficiency.
Keep 1.00 for heaters, kettles and incandescent lights. Use 0.85 for a typical motor when the nameplate does not list it.
Check the amps, kVA, suggested breaker and circuit load meter. Copy the result or share a link in one tap.
Benefits
Knowing the current a load draws keeps circuits safe, prevents nuisance trips and helps you buy the right cable, fuse or inverter.
Find out whether a space heater, kettle and microwave can share one circuit before the breaker trips, and plan where new appliances should go.
Run quick single-phase and three-phase load checks on site, with breaker sizes for both US and IEC panels and a working you can show the client.
Size 12 V, 24 V and 48 V cables, fuses and inverters from appliance wattage, then check cable losses with the voltage drop calculator.
See exactly how power factor, apparent power and the √3 factor change the answer, with the formula shown for every single result.
Real world
A clamp meter reading rarely matches watts ÷ volts exactly. These are the usual reasons.
FAQ
It depends on the voltage. 1,000 watts draws 8.33 amps at 120 V, 4.35 amps at 230 V, 4.17 amps at 240 V and 83.3 amps at 12 V DC, assuming a power factor of 1.
For DC, divide watts by volts: I = P ÷ V. For AC single-phase, divide by volts times power factor: I = P ÷ (V × PF). For three-phase, use I = P ÷ (1.732 × V × PF) with the line to line voltage.
A 15 A circuit at 120 V can carry 1,800 W at most, but continuous loads should stay under 80%, which is 1,440 W. A 20 A circuit at 120 V handles 2,400 W peak and 1,920 W continuous.
A 1,500 W space heater draws 12.5 A at 120 V, 6.52 A at 230 V and 6.25 A at 240 V. On a 120 V, 15 A circuit that is 83% of the rating, so avoid running other large loads on the same circuit.
No. Current depends on voltage, so the same 1,000 W load draws twice as much current at 120 V as it does at 240 V. Check the appliance label or your supply voltage first.
Use 1.0 for resistive loads such as heaters, kettles and incandescent bulbs. LED drivers and electronics with power factor correction are usually 0.9 to 0.99. Induction motors typically run at 0.75 to 0.9, so 0.8 is a safe estimate when the nameplate does not say.
Multiply kW by 1,000, then divide by 1.732 × line to line voltage × power factor. For example, 10 kW at 400 V with a power factor of 0.85 draws 10,000 ÷ (1.732 × 400 × 0.85) = 16.98 A per line.
A 100 W device on 12 V DC draws 100 ÷ 12 = 8.33 A. If it runs through an inverter from a 12 V battery, add about 10% for inverter losses and plan for roughly 9.2 A.
Use the watts to amps calculator whenever you add an appliance, plan a new circuit or wire a solar or RV system. Then check cable losses, running costs and cooling loads with our related tools.
Calculate amps nowResults are estimates for planning. Always follow your local electrical code and use a licensed electrician for installation work.